Air conditioners RÖDA Error Codes

Error code Fault Possible cause Remedy

  

A0 Source malfunction Wrong phasing or phase failure Determine the cause and then make the correct connection

Supply

  

C0 Remote Malfunction Poorly connected wires to Check the connection

(Wired) control unit of the remote unit of the remote unit

Or there is no connection

C1 Communication failure between the internal The wire is interrupted Contact the nearest service center.

And the outdoor unit by the indoor and outdoor unit

E1 Sensor fault Sensor defective Disconnect power and check the connection of the sensor. If this

Room temperature did not help - replace the sensor.

  

E2 Sensor fault Sensor defective Disconnect power and check the connection of the sensor. If it does not help, replace the sensor.

Temperature of the heat exchanger

Indoor unit

  

E4 Sensor fault Sensor defective Disconnect power and check the connection of the sensor. If it does not help, replace the sensor.

Temperature of the heat exchanger

Outdoor unit

  

H1 Tripping of the outdoor unit Defect the outdoor unit Determine the cause of the fault according to the fault indication on the outdoor unit display

Outdoor unit

  

H2 Triggering the protection system The temperature from the outside is too high. Find out the cause and fix it by

Compressor from overload to high or blocked capabilities

High pressure ventilation ducts

  Outdoor unit or clogged

  Filter / heat exchanger

  Outdoor unit


H3 Tripping of the protection system Temperature from the outside too Clear the cause and eliminate it by

Compressor from overload to low, or leakage occurred

Low pressure (vacuum) of the coolant from the system, or

  Pressure drops too

  Quickly when the coolant is pumped in

  Outdoor unit

H4 Tripping of the high sensor 1. Too much water The system automatically copes with the problem within 20 minutes.

The condensate level is formed in the cooling mode. During automatic elimination of the overflow problem with condensed water, only the "HEATING" and

  Room or dehumidification "VENTILATION" is available

  Room air. Or 1. The system is in locked

  Problems with the outflow of condensate. Condition. It is necessary to switch off the system and check the pump for evacuation of condensate water.

  2. If within 20 minutes. 2. After fixing the problem, turn on the air conditioner.

  System failed to cope with

  High level of condensate

  Water - sound sound

  alert

  

P1 Tripping of the protection system The protection system has tripped The system will return to the operating mode

Heat exchanger int. Automatically

From icing in mode

Cooling the room

P2 Tripping of the protection system The protection system has tripped The system will return to the operating mode

Heat exchanger internal automatically

Block from overheating in mode

Room heating

P3 Tripping of the protection system The protection system has tripped The system will return to the operating mode

External heat exchanger

Block from overheating in mode

Cooling the room

FF System failure The protection system has tripped. Switch off and on the air conditioner

  

P6 Cold supply protection The protection system has tripped The system will return to the operating mode

Air in heating mode automatically

Premises

P7 Icing (outdoor unit) The protection system has tripped The system will return to the operating mode

In room heating mode automatically

P8 Heating mode indicator The protection system has tripped The system will return to the operating mode

Compressor crankcase

CF Need indicator Filter contamination Switch off the air conditioner and

Cleaning or changing filters filter cleaning.